Output: 24 VDC @ 9.0 A (9.0 A total from all notification circuits and auxiliary circuit). |
Amps per output circuit: 3.0 A. |
Current draw of unit on battery: 75 mA standby, 175 mA in alarm. |
Auxiliary power circuits: 1. |
Notification circuits: 4. |
Output configuration options: 2 Class A (Style Z); 4 Class B (Style Y); or 1 Class A and 2 Class B. |
Notification circuit output: 20.4 to 27.3 VDC @ 3.0 A each. |
Inputs: 2, with configuration 2 Class B or 2 Class A. |
Input voltage range: 9 - 32 VDC. |
Battery charging capacity: 33.0 AH. |
Ambient temperature rating: 32°F to 120°F (0°C to 49°C). |
Relative humidity: 85% non-condensing maximum. |
Dimensions: 16.0" H x 12.25" W x 3.0" D (cm: 40.64 H x 30.88 W x 7.62 D). |
Indicator lights: AC Power On (green), Battery Trouble (yellow), Ground Fault (yellow), Aux Trouble (yellow), Output Troubles (1 – 4, yellow). |
UL Listed: file S6677. |
CSFM: 7300-1637:103 |