Primary (AC) Power
– 120 VAC 60 Hz, 3.2 A maximum
– Wire size: minimum 14 AWG (2.0 mm²) with 600V insulation. |
|
Control Input Circuit
– Trigger Input Voltage: 9.0 to 32 VDC.
– Trigger Current: 2.0 mA (16 - 32 V).
– (per input) 1.0 mA (9 - 16 V). |
|
Trouble Contact Rating – 5.0 A at 24 VDC. |
|
Auxiliary Power Output – Specific Application Power - 500 mA maximum. |
|
Output Circuits
– +24 VDC filtered, regulated.
– 3.0 A maximum for any one circuit.
– 4.0 A maximum total continuous current for all outputs (Stand-alone mode)
– 6A or 8A (depending on model) maximum total short-term current for all outputs (NAC Expander mode). |
|
Secondary Power (Battery) Charging Circuit
– Supports lead-acid batteries only.
– Float Charge Voltage: 27.6VDC.
– Maximum Charge Current: 1.5 A.
– Maximum Battery Capacity: 18 AH. |
|
UL Listed NAC Synchronization using System Sensor, Wheelock or Gentex (Commander Series) appliances. |
|
Cascade up to 10 power supplies (four with Gentex) with strobe timing maintained. |
|
Operates as a sync follower or a sync generator (default). |
|
Contains two, fully-isolated input/control circuits (triggered from FACP Notification Appliance Circuit [NAC expander mode] or jumpered permanently on [standalone mode]). |
|
Configured to internally house addressable SLC control module for alarm activation. |
|
Four Class B (Style Y) or four Class A (Style Z) (with ZNAC- 4 Module) Notification Appliance Circuits. |
|
6.0A or 8A (depending on model) full load output (3.0 A maximum per circuit) in NAC expander mode (UL 864). |
|
4.0A or 6.0A continuous output in stand-alone mode (UL 1481). |
|
In stand-alone mode, output power circuits may be configured as resettable (reset line from FACP required) or n onresettable or a mix of two and two. |
|
Fully regulated and filtered power output (optimal for powering four-wire smoke detectors, annunciators and other system peripherals requiring regulated/filtered power). |
|
Power-limiting technology meets UL power-limiting requirements. |
|
Form-C normally-closed trouble relay. |
|
Fully supervised power supply, battery and Notification Appliance Circuits. |
|
Selectable earth fault detection. |
|
AC trouble report selectable for immediate or 8 hour delay. |
|
Works with virtually any UL 864 fire alarm control which utilizes an industry-standard reverse-polarity notification circuit (including unfiltered and unregulated bell power). |
|
Requires input trigger voltage of 9.0 - 32 VDC. |
|
Self-contained in compact, lockable cabinet (15" [38.1 cm] H x 14.5" [36.8 cm] W x 2.75" [7.0 cm] D). |
|
Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet capable of housing 7.0 AH batteries. |
|
Battery charger may be disabled via dip switch for applications requiring larger batteries. |
|
Fixed, clamp-type terminal blocks accommodate up to 12 AWG (3.1 mm²) wire. |
|
UL Listed: UOXX.S6677, UTRZ.S6677 |
|
CSFM: 7315-1637:102 |
|
FM Approved |